- Dual colour coded scales for % and AC Voltage
- Neon indicator when voltage greater than 1200VAC is detected
- System Voltage 33kV
- Full Scale Voltage 36kV
- Maximum Voltage 40kV
- Frequency 50-60Hz
- Measures Phase to Phase
- Measures and tests Phase to Earth
- Compare between Phases
- High immunity to interference fields
- Current is limited to 1mA
- Lightweight, robust and compact
- Self-powered, no battery required
- Testing of grounded or ungrounded systems
- High quality fibreglass wound rod
- Suitable for indoor and outdoor use
- Meets IEC 61481
Description
The MT33KV 33kV High Voltage Phasing Stick is an all-in-one meter including a Phase Comparator with colour coded scale indication, a Voltage Detector with Neon Indication and a Scaled Voltmeter. This Multifunction Phasing Stick utilizes a long established technique to detect and measure high voltages and perform phasing tests. This dual pole instrument incorporates modern, high quality glass fibre front ends, composite polyurethane main body moulding to give tough and very lightweight construction and superior safety features. It has an analogue colour coded dual scales and neon indication. The dual scale read direct (no multiplier) in kVAC or in % of full scale and is colour coded (Green = in phase, Red = out of phase). A bright neon is included on the scale for easy visibility indoor and it has dual purpose. The neon is also a detector and will be lit when the voltage across the poles is higher than 1200VAC. In case of unlikely failure of the analogue scale indicator, the neon can be used as voltage detector.
This 33kV High Voltage Phasing Stick is housed in a superb high quality modern plastic case with shock absorbing foam. It is ideally suited for testing of grounded or ungrounded systems. Important applications include checking voltage fuses, testing for correct phase connections, and for absence of high voltage on de-energized lines or apparatus.
Specification
Function |
Range |
System voltage |
33kV |
Full scale voltage |
36kV |
Maximum voltage |
40kV |
Frequency |
50 or 60Hz |
Total resistance |
19.68MΩ |
Response time |
<1sec |
Neon threshold |
1.2kV |
Neon Lit fully @ |
1.5kV |
Display |
Neon & panel meter |
Length of handle |
775mm |
Length front end |
665mm |
Total length |
1.440m |
Total weight |
2.4kg |
Handle material |
Composite Material with polyurethane |
Front end material |
Fibre glass wound tubing |
Operating temperature |
-25°C to 55°C |
Operating humidity |
20 to 96% RH |
Safety standard |
IEC61481 |
We offer expert Calibration Service Australia Wide
- Fastest Calibration Service in Australia as fast as 24 Hrs Hight Priority
- Best In-House and On-Site Calibration Service in Entire Australia
- Smart Software based Calibration Service to reduce human error and improve uncertainty
- Mobile Calibration Service to reduce downtime and improve productivity
- ISO 17024 NATA Accredited Calibration Service