Product Type |
32 Channel gas monitor |
Operating Voltage |
12V to 35V DC or 120V AC (optional) |
Current Draw |
300 mA (at 24V DC) |
Power Supply |
6.25A (150W), 85/264V AC to 24V DC (optional) |
Customizable Settings |
Option to disable alarm relays |
Protection |
Power electromagnetic interference (EMI) filter
4-20 mA surge suppression
RS-485 surge suppression
|
Display Screen |
800 x 480 Resolution
7 inch resistive touchscreen
|
Interface |
Touchscreen |
Temperature Range |
-20°C to +50°C |
Wireless (Digital), Wired (Analog) Input |
Up to 32 Wireless sensor inputs, up to 4 can be 4-20 mA wired analog inputs |
Digital Output |
RS-485 Modbus |
Alarm Indications |
Optional strobe and audible alarm installed on housing (uses 1 or 2 relays) |
Relays |
• 4 Dry-contact relays with 4 amp replaceable fuses
• Individually set full scale, normally open or normally closed, latching or non-latching and fault terminal
|
Product Compatibility |
Wireless: All AirLink gas detector head transmitters
Wired (4-20mA): M2A, S2, T2A, T3A, VOC Pro, and Air Alert
|
Wireless Radio Options |
900 MHz radio
2.4 GHz radio
|
Networks |
52 Networks (900 MHz radio)
78 Networks (2.4 GHz radio)
255 Addresses per network
|
Enclosure Materials |
NEMA-4X fiberglass enclosure with clear window |
Add On Hardware |
Optional strobe and/or horn attached (uses one relay) |
Product Dimensions |
12 in, L x 10 in. D x 6 in. H (Max. dimensions with attachments) |
Total Weight |
12.15 lbs |
Product Mounting |
4 Mounting feet, 6 in. D x 12-1/4 in. T (included), Maximum mounting bolt/screw size of 5/16 in. (8mm) diameter |
Hardware Warranty |
1-Year limited |