Power Supply: |
12-28VDC, 200mA |
Span Stability: |
<0.007% FSO/ºC (PT112LC <0.005% FSO/ºC) |
Non-linearity: |
<0.01% FSO/ºC |
Load Cell Excitation: |
5V, up to 4x 350Ω or 8x 700Ω load cells, 4 wire connection PT112LC up to 8x 350Ω, 16x 700Ω load cells |
Input range: |
0mV to +20mV, PT112LC -18mV to +18mV |
Zero Adjustment Range: |
-19mV to +19mV PT112LC -18mV to +18mV |
Span adjustment range: |
0.2mV/V to 4mV/V input for full output PT112LC 0.16mV/V to 3.6mV/V |
Resolution: |
Internal 16000000/External 65000, 24 bit ADC/16 bit DAC |
Response speed: |
PT110LC fixed 500ms, PT111LC adjustable PT112LC adjustable to 25ms fastest. |
Annunciators: |
Run, Current/voltage mode, Error |
Front panel: |
2 Rotary switches, 3 LEDs on the front panel. |
Operating Environment: |
-10ºC to 45ºC (14ºF to 113ºF); max. 85% RH, non-condensing. IP20 |
Enclosure and Dimensions: |
Polyamide, DIN-rail mount, IP20, Front Width:22.5 x Height: 99, Depth:114.5, weight 0.45kg |
Mounting: |
DIN rail 35 mm x 7.5 mm, DIN 46277-3 |
Isolation: |
Common ground connection (VDC, GND). EMC Immunity Class E2. |
|
Analogue Output: |
0-10VDC or 4-20mA (PT110LC), 0-10VDC or 0-5VDC or 4-20mA or 0-20mA (PT111LC, PT112LC), Modbus & ±10V (PT112LC-MB). |
Programmable Setpoint output: |
PT110LC;- none, PT111LC, PT112LC;- 2 relay set points, 230 VAC, 0.5 A |
RS-232C: |
PT110LC;- none, PT111LC, PT112LC;- Set up and calibration with PC, PLC and AzCom software |
Calibration: |
PT110LC;- Performed with rotary switches on the front of the instrument. PT111LC, PT112LC;- Performed with rotary switches on the front of the instrument. With AzCom, can be performed via PC without calibration weights. |
Electronic Calibration: |
PT110LC;- no. PT111LC, PT112LC;- YES. |
Fast Calibration: |
PT110LC;- no. PT111LC, PT112LC;- YES. |
Digital Filter: |
PT110LC;- Fixed. PT111LC;- 3 step adjustable digital adaptive filter adjusted via PC with AzCom. PT112LC;- 9 step adjustable digital adaptive filter adjusted via PC with AzCom. |
|